Type 42-36E Pressure-independent Control Valve (PICV)
Application: Self-operated regulators for flow rate control in district heating systems or large heating or cooling networks. Combined with an electric actuator used to transmit the control signal of an electric controller. Valves DN 15 to 250 1) · Pressure rating PN 16 to 40 · Suitable for liquids, air and non-flammable gases from 5 to 150 °C
Combined self-operated regulator for flow rate with additional electric actuator
Nominal diameter DN 15…250
Nominal pressure PN 16…40
Globe valve with flanges single seat unbalanced / balanced
Valve body made of cast iron EN-GJL-250, Spheroidal graphite
iron EN-GJS-400-18-LT, Cast steel 1.0619 or stainless steel 1.4408
Reduced Kvs-values are standard
Flow set points from 0.5 to 220 m³/h / 2.2 to 969 US gal/min